Drinking-Water Systems Regulation 0. Reg. 170/03
Turbidity Chlorine | Number of Samples 365365 | Range of Results (min#)-(max#) 0.02 - 0.261.19 -1.63 | Unit of Measure NTUmg/L |
---|
Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.
Date of legal instrument issued | Parameter | Date Sampled | Running Annual Average Result | Un it of Measure |
---|---|---|---|---|
MDWL 025-101 | Bromate - Treated | 1-Jan-19 to 31-Dec-19 | <0.003 | mg/L |
MDWL 025-101 | Bromate - Distribution | 1-Jan-19 to 31-Dec-19 | <0.003 | mg/L |
- * Reported as Running Annual Average
- Summary oflnorganic parameters tested during this reporting period or the most recent sample results.
Parameter | Sample Date | Result Value | Unit of Measure | Exceedence |
---|---|---|---|---|
Antimony | October 2, 2019 | 0.00011 | mg/L | NO |
Arsenic | October 2, 2019 | 0.0003 | mg/L | NO |
Barium | October 2, 2019 | 0.0151 | mg/L | NO |
Boron | October 2, 2019 | 0.018 | mg/L | NO |
Cadmium | October 2, 2019 | 0.000003 <MDL | mg/L | NO |
Chromium | October 2, 2019 | 0.00018 | mg/L | NO |
*Lead | October 2, 2019 | 0.00002 | mg/L | NO |
Mercury | October 2, 2019 | 0.00001 <MDL | mg/L | NO |
Selenium | October 2, 2019 | 0.0001 | mg/L | NO |
Sodium | January 23, 2019 | 7.71 | mg/L | NO |
Uranium | October 2, 2019 | 0.000032 | mg/L | NO |
Fluoride | January 23, 2019 | 0.10 | mg/L | NO |
Nitrite | October 2, 2019 | 0.003 <MDL | mg/L | NO |
Nitrate | October 2, 2019 | 0.216 | mg/L | NO |
- Summary of lead testing under Schedule 15.1 during this reporting period
- (applicable to the following drinking water systems; large municipal residential systems, small municipal residential systems, and non-municipal year-round residential systems)
Location Type | Number of Samples | Range of Lead Results (min#)-(max#) | Unit of Measure | Number of Exceeedances |
---|---|---|---|---|
Plumbing | 278 | 0.01 <MDL - 10.80 | ug/L | 2 |