Incident Date Parameter Result Unit of Measure Corrective Action Corrective Action Date
May 22,2019 AWQI#145465 Count of 3 TC at Sample Station D22 Free chlorine residua l of 0.90mg/L 3 CFU/100mL Testing. 2 sets taken 24 hours apart initial location, downstream and upstream May 24,2019
July 30,2019 AWQI#l46916 Free chlorine residual of 0.03 mg/L at a hydrant 0.03 mg/L Flushing for 95 minutes restored the Free chlorine residual to 0.27 mg/L July 30,2019
December 13,2019 AWQI#l49264 Lead of 54.2 µg/L at a hydrant 54.2 µg/L Re-sample 2 consecutive days. Lead results of0.69µg/L and 0.34 µg/L were obtained. December 20,2019

Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03, during this reporting period.

  Number of Range of E.Coli Range of Total Coliform Number of Range of HPC
Samples (min#)-(max#) (min#)-(max#) HPC Samples (min#)-(max#)
Raw 248 2-400 10 - 3400 248 40->2000
Treated 1855 0-0 0-0 1466 <10- 50
Distribution 1852 0-0 0-3 957 <10- 50

NOTE: For continuous monitors use 8760 as the number of samples.